ABB Breaker S203-C10
7 days
Number of Poles:3 | Rated Frequency (f): |
Tripping Characteristic:C | 50 Hz |
Rated Current (In):10 A | 60 Hz |
Rated Operational Voltage: | Rated Short-Circuit Capacity (Icn): |
acc. to IEC 60898-1 400 V AC | (400 V AC) 6 kA |
acc. to IEC 60947-2 440 V AC | Rated Ultimate Short-Circuit Breaking Capacity (Icu): |
Power Loss:6.3 W | (230 V AC) 20 kA |
at Rated Operating Conditions per Pole 2.1 W | (440 V AC) 10 kA |
Rated Insulation Voltage (Ui): | Rated Service Short-Circuit Breaking Capacity (Ics): |
acc. to IEC/EN 60664-1 440 V | (230 V AC) 15 kA |
Operational Voltage: | Energy Limiting Class:3 |
Maximum (Incl. Tolerance) 440 V AC | Overvoltage Category:III |
Maximum 440 V AC | Pollution Degree:3 |
Minimum 12 V AC | Rated Impulse Withstand Voltage (Uimp):4 kV |
Minimum 12 V DC | (6.2 kV @ sea level) |
Dielectric Test Voltage:50 / 60 Hz, 1 min: 2 kV | (5.0 kV @ 2000 m) |
Housing Material:Insulation Group II, RAL 7035 | Actuator Type:Insulation group II, black, sealable |
Contact Position Indication:Red ON / Green OFF | Degree of Protection:IP20 |