LC1D09B7C
contactor TeSys LC1-D - 3 poles - AC-3 440V
9 A - coil 24 V AC
Main
Range of product | TeSys D |
Product or component type |
Contactor |
Device short name | LC1D |
Contactor application |
Motor control Resistive load |
Utilisation category |
AC-1 AC-3 |
Control circuit type | AC |
Coil type | AC 50/60 Hz |
Poles description | 3P |
Pole contact composition | 3 NO |
[Ie] rated operational current |
25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit 9 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit |
Motor power kW |
4 kW at 380...400 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz 5.5 kW at 660...690 V AC 50/60 Hz 4 kW at 415...440 V AC 50/60 Hz |
Motor power hp |
0.5 hp at 115 V AC 60 Hz for 1P motors conforming to CSA 0.5 hp at 115 V AC 60 Hz for 1P motors conforming to UL 1 hp at 230/240 V AC 60 Hz for 1P motors conforming to CSA 1 hp at 230/240 V AC 60 Hz for 1P motors conforming to UL 2 hp at 200/208 V AC 50/60 Hz for 3P motors conforming to CSA 2 hp at 200/208 V AC 50/60 Hz for 3P motors conforming to UL 2 hp at 230/240 V AC 50/60 Hz for 3P motors conforming to CSA 2 hp at 230/240 V AC 50/60 Hz for 3P motors conforming to UL 5 hp at 460/480 V AC 50/60 Hz for 3P motors conforming to CSA 5 hp at 460/480 V AC 50/60 Hz for 3P motors conforming to UL 7.5 hp at 575/600 V AC 50/60 Hz for 3P motors conforming to CSA 7.5 hp at 575/600 V AC 50/60 Hz for 3P motors conforming to UL |
[Uc] control circuit voltage | 24 V AC 50/60 Hz |
Connections - terminals |
Control circuit: ring lugs - external diameter: 8 mm Control circuit: spring terminal 1 cable 2.5 mm² - cable stiffness: flexible - without cable end Control circuit: spring terminal 2 cable 2.5 mm² - cable stiffness: flexible - without cable end Power circuit: ring lugs - external diameter: 8 mm Power circuit: spring terminal 1 cable 2.5 mm² - cable stiffness: flexible - without cable end Power circuit: spring terminal 2 cable 2.5 mm² - cable stiffness: flexible - without cable end Control circuit: screw clamp terminal 1 cable 1...4 mm² - cable stiffness: flexible - without cable end Control circuit: screw clamp terminal 2 cable 1...4 mm² - cable stiffness: flexible - without cable end Control circuit: screw clamp terminal 1 cable 1...4 mm² - cable stiffness: flexible - with cable end Control circuit: screw clamp terminal 2 cable 1...2.5 mm² - cable stiffness: flexible - with cable end Control circuit: screw clamp terminal 1 cable 1...4 mm² - cable stiffness: solid - without cable end Control circuit: screw clamp terminal 2 cable 1...4 mm² - cable stiffness: solid - without cable end Power circuit: screw clamp terminal 1 cable 1...4 mm² - cable stiffness: flexible - without cable end Power circuit: screw clamp terminal 2 cable 1...4 mm² - cable stiffness: flexible - without cable end Power circuit: screw clamp terminal 1 cable 1...4 mm² - cable stiffness: flexible - with cable end Power circuit: screw clamp terminal 2 cable 1...2.5 mm² - cable stiffness: flexible - with cable end Power circuit: screw clamp terminal 1 cable 1...4 mm² - cable stiffness: solid - without cable end Power circuit: screw clamp terminal 2 cable 1...4 mm² - cable stiffness: solid - without cable end |
Coil technology | Without built-in bidirectional peak limiting diode suppressor |
Protective cover | With |
Auxiliary contacts type |
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1 Type mirror contact (1 NC) conforming to IEC 60947-4-1 |
Auxiliary contact composition | 1 NO + 1 NC |
Control circuit voltage limits |
0.3...0.6 Uc at 60 °C drop-out 50/60 Hz 0.8...1.1 Uc at 60 °C operational 50 Hz 0.85...1.1 Uc at 60 °C operational 60 Hz |
[Ui] rated insulation voltage |
600 V for control circuit certifications CSA 600 V for control circuit certifications UL 600 V for power circuit certifications CSA 600 V for power circuit certifications UL 690 V for control circuit conforming to IEC 60947-1 690 V for power circuit conforming to IEC 60947-1 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
Overvoltage category | III |
Mounting support |
Plate Rail |
Flame retardance | V1 conforming to UL 94 |
Tightening torque |
Control circuit: 1.7 nm - on screw clamp terminal - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminal - with screwdriver Philips No 2 Power circuit: 1.7 nm - on screw clamp terminal - with screwdriver flat Ø 6 mm Power circuit: 1.7 nm - on screw clamp terminal - with screwdriver Philips No 2 |
[Ue] rated operational voltage | <= 690 V AC 25...400 Hz for power circuit |
[Ith] conventional free air thermal current |
10 A at <= 60 °C for control circuit 25 A at <= 60 °C for power circuit |
Irms rated making capacity |
250 A at 440 V for power circuit conforming to IEC 60947 250 A DC for control circuit conforming to IEC 60947-5-1 |
Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
Associated fuse rating |
10 A gG for control circuit conforming to IEC 60947-5-1 20 A gG at <= 690 V coordination type 2 for power circuit 25 A gG at <= 690 V coordination type 1 for power circuit |
Average impedance | 2.5 mOhm at 50 Hz - Ith 25 A for power circuit |
Power dissipation per pole |
0.2 W AC-3 1.56 W AC-1 |
Inrush power in VA | 70 VA at 20 °C (cos φ 0.75) |
Hold-in power consumption in VA | 7 VA at 20 °C (cos φ 0.3) 50 Hz |
Operating time |
20 ms opening 12...22 ms closing |
Safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Mechanical durability | 15000000 cycles |
Operating rate | 3600 cyc/h at <= 60 °C |
Minimum switching current | 5 mA for control circuit |
Minimum switching voltage | 17 V for control circuit |
Non-overlap time |
1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts |
Insulation resistance | > 10 MOhm for control circuit |
Height | 77 mm |
Width | 45 mm |
Depth | 84 mm |
Product weight | 0.5 kg |
Standards |
CSA C22-2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
Product certifications |
BV CCC CSA DNV (Det Norske Veritas) GL GOST LROS (Lloyds register of shipping) RINA UL |
IP degree of protection |
IP2x conforming to IEC 60529 IP2x conforming to VDE 0106 |
Protective treatment | TH (pollution degree: 3) conforming to IEC 60068 |
Ambient air temperature for operation | -5...60 °C |
Ambient air temperature for storage | -60...80 °C |
Permissible ambient air temperature around the device | -40...70 °C at Uc |
Operating altitude | 3000 m without derating in temperature |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Shock resistance |
10 gn contactor opened 15 gn contactor closed |
Vibration resistance |
2 gn 5...300 Hz contactor opened 4 gn 5...300 Hz contactor closed |
Heat dissipation | 2...3 W at 50/60 Hz for control circuit |
Contact Information:
Wechat: +86 133 5926
9377
Email: rig123@rig123.com
Skype: liuyongjie67
QQ: 526354062
If you have any questions,pls do not hesitate to contact
us .
Attention: Please kindly leave us your phone number
,and also a full and accurate shipping address.
Remark : please kindly add our email to your "white-list" or sign"important" then you can get our message
successfully every time,like special offer, promotion sale ,technic info , and
so on ,thanks !